Tags: Generator Inlet Exhaust

4 FAQs about Generator inlet and exhaust air temperature requirements

What temperature should a generator be rated at?

o pull a rated full load between 40°C (104°F) and 50°C (122°F). The cooling systems are designed to operate in these ambients, and when enclosed, he canopy design has to allow the correct amount of air in and out. While a generator's rated power output will be reduced as the ambient air temperature increases above 21°C (70°F), the

Does a generator room need ventilation?

When the engine and alternator are running, heat is emitted, which increases the temperature of the air in the room. Therefore, in order to limit the increase in temperature in the room and supply clean, cold air to the engine, it is necessary to have ventilation in the generator room. Figure 5.1.

What if the engine room temperature exceeds 40°C?

If the engine room temperature exceeds 40°C (104°F), the generator must be derated per the generator derate schedule and cool outside air must be ducted directly to the generator air intake. Alternatively, custom generators can be sized to handle specific ambient conditions.

Should a generator air inlet be facing the wind?

When ever possible, face the generator air inlet openings away from the wind. The wind can prevent the air intake louver from opening on start up. The air inlet must be capable of moving enough air through the room to provide the correct minimum CFM (cubic feet per minute) cooling for generator as specified by the generator's manufacturer.

View/Download Generator inlet and exhaust air temperature requirements [PDF]

PDF version includes complete article with source references. Suitable for printing and offline reading.